ข้ามสารบัญไปยังเนื้อหา
อัปเดต 2026-09-07
Hazardous-area project (SoRS)
IEC 60079-10-1 · EI 15 · API RP 505
Manages a multi-source Hazardous Area Classification project and builds a 31-column Source-of-Release Schedule (SoRS) per IEC 60079-10-1, EI 15, and API RP 505 — computing release rate, zone extent, and recommended Ex marking, gas group, and temperature class per source, and exporting a datasheet per source for the electrical design team.
เมื่อไรจึงใช้
- Classifying Zone 0/1/2 areas around every flammable release source on a plot, not just one calculator run.
- Handing the electrical/instrumentation team a formal SoRS with per-source Ex equipment requirements.
ค่าที่ต้องกรอก
| ค่า | คำอธิบาย |
|---|---|
| Release source data | Fluid, hole size / grade of release, and ventilation, per source — one row per SoRS entry. |
| Ventilation availability & dilution | Sets the zone type (0/1/2) and its extent per IEC 60079-10-1. |
คำนวณอย่างไร
Each source is classified independently per IEC 60079-10-1's release-rate and dispersion method, then rolled into the standard 31-column SoRS format the electrical design discipline expects, with CSV/PDF export and a per-source datasheet.
ข้อควรระวัง
noteZone classification is source-by-source — overlapping zones from adjacent sources still need an engineering judgment call on which governs a shared area.
ที่เกี่ยวข้อง