Air duct sizing
ASHRAE Fundamentals Ch.21
Sizes round or rectangular HVAC ductwork, converting rectangular geometry to an equivalent round diameter and reusing the Darcy–Weisbach hydraulic core from the liquid-pipe module.
คำนวณอย่างไร
Same Darcy–Weisbach + Swamee–Jain friction-factor machinery as the pressure-drop calculator, with ASHRAE Table 21-1 duct-material roughness and an equivalent-diameter conversion (Huebscher 1948) for rectangular ducts.
สมการ
Duct pressure drop (Darcy–Weisbach)
identical hydraulic core to the liquid pressure-drop calculator; D is the (equivalent) duct diameter
Equivalent round diameter (Huebscher 1948)
ASHRAE 2021 eq 21-1; a,b = rectangular duct sides (m) — gives the round duct with the same ΔP at the same flow