Psychrometric Properties
ASHRAE Fundamentals 2021 Ch.1 — Hyland-Wexler moist air
Full moist-air state (dry-bulb, wet-bulb, dew-point, relative humidity, humidity ratio, enthalpy, specific volume) from any consistent pair of inputs, at a given total or altitude-derived atmospheric pressure.
คำนวณอย่างไร
Evaluates the Hyland-Wexler saturation-pressure correlation, derives the humidity ratio from the partial/total pressure ratio, and closes the remaining state via the ASHRAE moist-air enthalpy relation; wet-bulb and dew-point are recovered by bracketed bisection / Newton-Raphson root-finding on their respective ASHRAE energy-balance and saturation relations (converges in a few iterations, never throws on unsolvable/supersaturated input).
สมการ
Humidity Ratio
ASHRAE 2021 Ch.1 eq.22; W in kg water vapor / kg dry air; 0.621945 = M_water/M_dry-air.
Specific Enthalpy of Moist Air
ASHRAE 2021 eq.30; c_pa=1.006, h_fg0=2501, c_pv=1.86 kJ/(kg·K); reference state dry air + liquid water at 0°C.
Saturation Vapor Pressure (Hyland-Wexler, over liquid water)
T in K, valid T≥0°C (ASHRAE 2021 eq.6); a parallel eq.5 over-ice branch is used below 0°C.